diff --git a/KTT-backup/KTT-backup.md b/KTT-backup/KTT-backup.md deleted file mode 100644 index d97860ed6531f2b35b3979892cfa4207eeb12beb..0000000000000000000000000000000000000000 --- a/KTT-backup/KTT-backup.md +++ /dev/null @@ -1,15 +0,0 @@ ---- -layout: page -permalink: /internal/lab/KTT-backup/ -shortcut: lab:KTT-backup -redirect_from: - - /cards/lab:KTT-backup - - /internal/cards/lab:KTT-backup ---- -# ketterthill cold storage backup plan - -To rescue Ketterthill’s reagents, security guard 5555 will ask you to come on site and give support to place their 8 shelves in our Cold storage room BT2 SS1-003A as illustrated on the drawing (Appendix 05). A person from Ketterthill will wait for you on the parking at -1st floor. - -Notify the LCSB duty call manager and their backup by email, fill the “Duty call report form†(https://ulsurvey.uni.lu/index.php/936567?lang=en) - - diff --git a/incubator_failure/incubator_failure.md b/incubator_failure/incubator_failure.md deleted file mode 100644 index a4ab3f002268fb3d06e97c6845ff69206f08f55e..0000000000000000000000000000000000000000 --- a/incubator_failure/incubator_failure.md +++ /dev/null @@ -1,26 +0,0 @@ ---- -layout: page -permalink: /internal/lab/incubator_failure/ -shortcut: lab:incubator_failure -redirect_from: - - /cards/lab:incubator_failure - - /internal/cards/lab:incubator_failure ---- - -# P3: Incubator failure - -This process does not concern LCSB0814 and LCSB1047 in BT2, 3rd floor, room 310 (See "P4: Zebrafish incubator temperature problem"). -This process applies in case of problem with temperature or gas (N2 or CO2) levels of an incubator. - -1. If after 20 minutes, the trend does not go back to the initial settings. -2. If you suspect an open door, you can ask a security guard to close it (+352 46 66 44 5555). -3. If it is not the problem, come on site to evaluate the situation. -4. If the issue cannot be fixed on site, transfer the samples to another incubator in the same room with the same temperarure and gas setting. - -Personal protective equipment --Lab coat --Gloves - -5. Keep track of what was moved where. -6. Notify the LCSB duty call manager and their back up by email, and fill the "Duty call report form" (https://ulsurvey.uni.lu/index.php/936567?lang=eng) - diff --git a/p.5.1_replacement-gas-bottles_BT1-2/p.5.1_replacement-gas-bottles_BT1-2.md b/p.5.1_replacement-gas-bottles_BT1-2/p.5.1_replacement-gas-bottles_BT1-2.md deleted file mode 100644 index 7f58228352cf6eb6959d8f13922802d84279acc5..0000000000000000000000000000000000000000 --- a/p.5.1_replacement-gas-bottles_BT1-2/p.5.1_replacement-gas-bottles_BT1-2.md +++ /dev/null @@ -1,71 +0,0 @@ ---- -layout: page -permalink: /internal/lab/p.5.1_replacement-gas-bottles_BT1-2/ -shortcut: lab:p.5.1_replacement-gas-bottles_BT1-2 -redirect_from: - - /cards/lab:p.5.1_replacement-gas-bottles_BT1-2 - - /internal/cards/lab:p.5.1_replacement-gas-bottles_BT1-2 ---- -# P5.1: Replacement of N2 or CO2 gas bottles (BT1/BT2) - -This section describes the procedure for replacement of gas bottles. -If you receive an alarm on the gas, you need to come to LCSB. - -1. A first method to identify which type of bottle is empty is to check on the gas panel in the corridor of the 4th floor in BT1 and room 104, 1st floor in BT2. - -<div align="center"> -<img src="p5.1_img_01.jpg" height="200"> -</div> - -* If one LED is on, one couple of bottle is empty, only one couple of bottles needs to be replaced. -* If two LEDs are on (left and right), both couple of gas bottles are empty and need to be replaced urgently. - -2. Press the reset button to stop the beeping. - -3. A second way to identify which type of gas and which couple of bottles is empty, is to directly check the manometers in the gas deposit rooms. -If the manometer (5 in the picture below) displays 0 bar, this means that the couple of bottles is empty. - -4. If you can see on the “Gas Bottle Exchange Sheet†in the room that the CO2 bottles have already been changed in the 48 h prior to the alarm, this is indicative of a pipeline infrastructure break down → see P6: gas network total failure back up plan. - -5. Replace the empty bottles in room 005 of BT1 or LT03 of BT2, ground floor - -|*Personal protective equipment*| -|:-----------------------------:| -|Lab coat| -|Safety goggles| - -<div align="center"> -<img src="p5.1_img_02.jpg"> -</div> - -* Check the gas level on the manometer (5 on the picture). When empty, it displays 0 bar. -* Once the bottles that need to be changed have been identified, close the network valve (3 on the picture) -* Close the bottles (1 on the picture) -* Open the purge valve (4 on the picture) to release the pressure remaining in the pipe connecting the bottle, then close back the purge valve -* Unscrew the tubing from the bottle by hand (2 on the picture) -* Move the empty bottle to the bottle rack, bring the new bottle and fasten the chain -* Connect the new bottle by screwing the tubing hand tight (2 on the picture) -* Open the gas bottle (1 on the picture) -* Check for leaks at the connection between the bottle and the tubing -* Open the purge valve (4 on the picture) for 2 seconds to fill the tubing with gas and remove the air, then close it back -* Open the network valve (3 on the picture) - -6. Check for any leak after connecting the bottle using the leak detector spray located in the gas deposit room, an example is shown on the picture below - -<div align="center"> -<img src="p5.1_img_03.jpg" height="250"> -</div> - -7. Fill up the “gas bottle exchange record sheet†(Appendix 03) on the door inside the gas deposit room. A copy of this document is present in each gas deposit room - -<div align="center"> -<img src="p5.1_img_04.jpg"> -</div> - -8. Check in the LIMS if the alert is resolved - -9. Notify the LCSB duty call manager and their backup by email, fill and fill the: -[Duty call report form](https://ulsurvey.uni.lu/index.php/936567?lang=en) - - - diff --git a/p.5.1_replacement-gas-bottles_BT1-2/p5.1_img_01.jpg b/p.5.1_replacement-gas-bottles_BT1-2/p5.1_img_01.jpg deleted file mode 100644 index 1884c6e167e83dcd4d03f61d489df011f1821f81..0000000000000000000000000000000000000000 Binary files a/p.5.1_replacement-gas-bottles_BT1-2/p5.1_img_01.jpg and /dev/null differ diff --git a/p.5.1_replacement-gas-bottles_BT1-2/p5.1_img_02.jpg b/p.5.1_replacement-gas-bottles_BT1-2/p5.1_img_02.jpg deleted file mode 100644 index 0a6d9d42681ef4086212a22e08d7303b751aa46b..0000000000000000000000000000000000000000 Binary files a/p.5.1_replacement-gas-bottles_BT1-2/p5.1_img_02.jpg and /dev/null differ diff --git a/p.5.1_replacement-gas-bottles_BT1-2/p5.1_img_03.jpg b/p.5.1_replacement-gas-bottles_BT1-2/p5.1_img_03.jpg deleted file mode 100644 index 166b05ab9b10954942223bb5999c3fb80e3e42be..0000000000000000000000000000000000000000 Binary files a/p.5.1_replacement-gas-bottles_BT1-2/p5.1_img_03.jpg and /dev/null differ diff --git a/p.5.1_replacement-gas-bottles_BT1-2/p5.1_img_04.jpg b/p.5.1_replacement-gas-bottles_BT1-2/p5.1_img_04.jpg deleted file mode 100644 index f972c4624d8ecba051ac8a8006b14118a85d1d0b..0000000000000000000000000000000000000000 Binary files a/p.5.1_replacement-gas-bottles_BT1-2/p5.1_img_04.jpg and /dev/null differ diff --git a/p.5.2_replacement-gas-bottles_BTA/p.5.2_img-1.jpg b/p.5.2_replacement-gas-bottles_BTA/p.5.2_img-1.jpg deleted file mode 100644 index 1a70b43c6097fb52dff10cdff1047de3603afb3e..0000000000000000000000000000000000000000 Binary files a/p.5.2_replacement-gas-bottles_BTA/p.5.2_img-1.jpg and /dev/null differ diff --git a/p.5.2_replacement-gas-bottles_BTA/p.5.2_img-2.jpg b/p.5.2_replacement-gas-bottles_BTA/p.5.2_img-2.jpg deleted file mode 100644 index 166b05ab9b10954942223bb5999c3fb80e3e42be..0000000000000000000000000000000000000000 Binary files a/p.5.2_replacement-gas-bottles_BTA/p.5.2_img-2.jpg and /dev/null differ diff --git a/p.5.2_replacement-gas-bottles_BTA/p.5.2_img-3.jpg b/p.5.2_replacement-gas-bottles_BTA/p.5.2_img-3.jpg deleted file mode 100644 index 85f882fe1207553966c728e410657c367d2f73d5..0000000000000000000000000000000000000000 Binary files a/p.5.2_replacement-gas-bottles_BTA/p.5.2_img-3.jpg and /dev/null differ diff --git a/p.5.2_replacement-gas-bottles_BTA/p.5.2_replacement-gas-bottles_BTA.md b/p.5.2_replacement-gas-bottles_BTA/p.5.2_replacement-gas-bottles_BTA.md deleted file mode 100644 index f88ea7a2e09e156d4820f4e9c634848c44861364..0000000000000000000000000000000000000000 --- a/p.5.2_replacement-gas-bottles_BTA/p.5.2_replacement-gas-bottles_BTA.md +++ /dev/null @@ -1,47 +0,0 @@ ---- -layout: page -permalink: /internal/lab/p.5.2_replacement-gas-bottles_BTA/ -shortcut: lab:p.5.2_replacement-gas-bottles_BTA -redirect_from: - - /cards/lab:p.5.2_replacement-gas-bottles_BTA - - /internal/cards/lab:p.5.2_replacement-gas-bottles_BTA ---- -# P5.2: CO2 Gas bottle replacement BTA -This section describes the procedure for replacement of gas bottles. - -1. Check when the bottle where exchanged for the last time on the “gas bottle exchange record sheetâ€. - -* If the CO2 bottles have already been changed in the 48 h prior to the alarm, change the bottles and immediately contact the Facility Manager (LCSB-INF-01-A-01) -* If the last change was made more than 48h before, change the bottles and contact the duty call manager (see below) - -2. Replace the empty bottles in room S130 - -<div align="center"> -<img src="p.5.2_img-1.jpg"> -</div> - -* Check the gas level on the manometer (5 on the picture). When empty, it displays 0 bar. -* Once the pair of bottles that need to be changed have been identified, close the network valve (3 on the picture) -* Close the bottles (1 on the picture) -* Open the purge valve (4 on the picture) to release the pressure remaining in the pipe connecting the bottles, then close back the purge valve -* Unscrew the tubing from the bottles by hand (2 on the picture) -* Move the empty bottles to the bottle rack, bring the new bottles and fasten the chains -* Connect the new bottles by screwing the tubing hand tight (2 on the picture) -* Open the gas bottles (1 on the picture) -* Check for leaks at the connection between the bottles and the tubing -* Open the purge valve (4 on the picture) for 2 seconds to fill the tubing with gas and remove the air, then close it back -* Open the network valve (3 on the picture) -* Check for any leak after connecting the bottle using the leak detector spray, an example is shown on the picture below - -<div align="center"> -<img src="p.5.2_img-2.jpg" height="250"> -</div> - -4. Fill up the “gas bottle exchange record sheet†(LCSB-INF-01-A-03) on the door inside the gas deposit room. -A copy of this document is present in each gas deposit room. - -<div align="center"> -<img src="p.5.2_img-3.jpg"> -</div> - -1. Notify the Facility Manager, the LCSB duty call manager and their backup by email and fill the [Duty call report form](https://ulsurvey.uni.lu/index.php/936567?lang=en) \ No newline at end of file diff --git a/p.8.1_cryo-storage_bt2/p.8.1_cryo-storage_bt2.md b/p.8.1_cryo-storage_bt2/p.8.1_cryo-storage_bt2.md deleted file mode 100644 index c6d0d5abbae8b19ca817dafccfe68524010b93a1..0000000000000000000000000000000000000000 --- a/p.8.1_cryo-storage_bt2/p.8.1_cryo-storage_bt2.md +++ /dev/null @@ -1,68 +0,0 @@ ---- -layout: page -permalink: /internal/lab/p.8.1_cryo-storage_bt2/ -shortcut: lab:p.8.1_cryo-storage_bt2 -redirect_from: - - /cards/lab:p.8.1_cryo-storage_bt2 - - /internal/cards/lab:p.8.1_cryo-storage_bt2 ---- -# P8.1 Cryo storage BT2 - -This section describes the procedure in the event of low nitrogen levels in both the cryo storage and cryocyl-120 tanks (BT2, room SS1 003). - -<div align="center"> -<img src="p8.1_img-1.jpg" height="300"> -</div> - -1. If the issue is not the nitrogen level and the temperature cannot be held below -120°C, transfer the content of the cryostorage to the back up -80°C freezer LCSB0709 in the same room, see “P6: Freezer failure back up planâ€. - - -|*Personal protective equipment*| -|:-----------------------------:| -|Lab coat| -|Cryogloves| -|Safety goggles| - - -2. If the issue comes from the nitrogen level, verify whether the cryocyl-120 tanks is empty by pressing on “press†on the level gauge panel: in that case, 0% is displayed - -<div align="center"> -<img src="p8.1_img-2.jpg" height="200"> -</div> - -3. If the cryocyl-120 is empty, it needs to be replaced by the liquid nitrogen tank standing in the same room. - -* Unplug the black wire (power supply) of the right data logger (FW-Z 0,5) and secure the probe on the dedicated rack on the cryocyl-120 tank. - -<div align="center"> -<img src="p8.1_img-3.jpg"> -</div> - -4. Close gas valve number 1 on the cryocyl-120 tank. - -<div align="center"> -<img src="p8.1_img-4.jpg"> -</div> - -5. Unscrew the tubing connected to valve 1 using the wrench available in the duty call toolbox in the gas deposit rooms (Appendix 04) - -6. Move the cryocyl-120 tank to the middle of the room - -7. Unscrew the tubing connected to the liquid nitrogen tank and place the tank next to the cryo storage tank - -<div align="center"> -<img src="p8.1_img-5.jpg" height="300"> -</div> - -8. Screw the tubing from the cryo storage tank to the “Filling, withdrawal valve†valve (valve 1) of the liquid nitrogen tank using the wrench available in the duty call toolbox in the gas deposit rooms (Appendix 04) - -9. Fully open valve 1, then close it back a ¼ turn - -<div align="center"> -<img src="p8.1_img-6.jpg"> -</div> - -10. Check that the liquid nitrogen percentage of the cryo storage tank increases (wait for 10 minutes) - -11. Notify the LCSB duty call manager and their backup by email, fill and fill the [Duty call report form](https://ulsurvey.uni.lu/index.php/936567?lang=en) - diff --git a/p.8.1_cryo-storage_bt2/p8.1_img-1.jpg b/p.8.1_cryo-storage_bt2/p8.1_img-1.jpg deleted file mode 100644 index e804862fe07430ee9bb442a448d397f2fdcf02e3..0000000000000000000000000000000000000000 Binary files a/p.8.1_cryo-storage_bt2/p8.1_img-1.jpg and /dev/null differ diff --git a/p.8.1_cryo-storage_bt2/p8.1_img-2.jpg b/p.8.1_cryo-storage_bt2/p8.1_img-2.jpg deleted file mode 100644 index ffbf57fbef847dc2b4424c0e7e8f75c269eaf21b..0000000000000000000000000000000000000000 Binary files a/p.8.1_cryo-storage_bt2/p8.1_img-2.jpg and /dev/null differ diff --git a/p.8.1_cryo-storage_bt2/p8.1_img-3.jpg b/p.8.1_cryo-storage_bt2/p8.1_img-3.jpg deleted file mode 100644 index c423db4c13ac6fc5550552e6d2857b36945b1ba1..0000000000000000000000000000000000000000 Binary files a/p.8.1_cryo-storage_bt2/p8.1_img-3.jpg and /dev/null differ diff --git a/p.8.1_cryo-storage_bt2/p8.1_img-4.jpg b/p.8.1_cryo-storage_bt2/p8.1_img-4.jpg deleted file mode 100644 index e9cdf4e4a554a5ebb8fbe830749cd9fe51d88bd0..0000000000000000000000000000000000000000 Binary files a/p.8.1_cryo-storage_bt2/p8.1_img-4.jpg and /dev/null differ diff --git a/p.8.1_cryo-storage_bt2/p8.1_img-5.jpg b/p.8.1_cryo-storage_bt2/p8.1_img-5.jpg deleted file mode 100644 index d6ff1f9a83dee1ec28676b78668d2024d7e63c75..0000000000000000000000000000000000000000 Binary files a/p.8.1_cryo-storage_bt2/p8.1_img-5.jpg and /dev/null differ diff --git a/p.8.1_cryo-storage_bt2/p8.1_img-6.jpg b/p.8.1_cryo-storage_bt2/p8.1_img-6.jpg deleted file mode 100644 index 20e8077e0eb0ed5e093c23a70a7d42400d1c26d1..0000000000000000000000000000000000000000 Binary files a/p.8.1_cryo-storage_bt2/p8.1_img-6.jpg and /dev/null differ diff --git a/p.8.2_cryostorage_bta/p.8.2_cryostorage_bta.md b/p.8.2_cryostorage_bta/p.8.2_cryostorage_bta.md deleted file mode 100644 index edddaa23ed3676779aa0c0adfb2532b03295f29f..0000000000000000000000000000000000000000 --- a/p.8.2_cryostorage_bta/p.8.2_cryostorage_bta.md +++ /dev/null @@ -1,19 +0,0 @@ ---- -layout: page -permalink: /internal/lab/p.8.2_cryostorage_bta/ -shortcut: lab:p.8.2_cryostorage_bta -redirect_from: - - /cards/lab:p.8.2_cryostorage_bta - - /internal/cards/lab:p.8.2_cryostorage_bta ---- - -# P8.2: Cryostorage BTA -1. If you receive an alarm for low levels of liquid nitrogen, do not come on site. - -2. The only case where you need to come is in the event of a temperature rise above - 80°C (however, if the nitrogen tank is empty, the temperature should be kept for a week. -There is no need to move the samples) - -3. If this happens, transfer the samples to the -80°C freezer - -4. Notify the Facility Manager, the LCSB duty call manager and their backup by email and fill the [Duty call report form](https://ulsurvey.uni.lu/index.php/936567?lang=en) - diff --git a/p3.2_incubator_failure_BTA/p3.2_incubator_failure_BTA.md b/p3.2_incubator_failure_BTA/p3.2_incubator_failure_BTA.md deleted file mode 100644 index f108b6534d8d518f09accffadf5a286be2715bc7..0000000000000000000000000000000000000000 --- a/p3.2_incubator_failure_BTA/p3.2_incubator_failure_BTA.md +++ /dev/null @@ -1,16 +0,0 @@ ---- -layout: page -permalink: /internal/lab/p3.2_incubator_failure_BTA/ -shortcut: lab:p3.2_incubator_failure_BTA -redirect_from: - - /cards/lab:p3.2_incubator_failure_BTA - - /internal/cards/lab:p3.2_incubator_failure_BTA ---- - -# P3.2: Incubator failure - -This process applies in the event of issues with temperature or gas levels of an incubator. - -1. Contact the Animal facility manager (See LCSB-INF-01 Appendix 01) and explain him the situation - -2. Notify the Facility Manager, the LCSB duty call manager and their backup by email and fill the [Duty call report form](https://ulsurvey.uni.lu/index.php/936567?lang=en) diff --git a/p6_gas-network-total-failure-backup-plan_bt1-2/p6_gas-network-total-failure-backup-plan_bt1-2.md b/p6_gas-network-total-failure-backup-plan_bt1-2/p6_gas-network-total-failure-backup-plan_bt1-2.md deleted file mode 100644 index 906fc79e864d1d0fcbf6127b25f5104e747e30a3..0000000000000000000000000000000000000000 --- a/p6_gas-network-total-failure-backup-plan_bt1-2/p6_gas-network-total-failure-backup-plan_bt1-2.md +++ /dev/null @@ -1,53 +0,0 @@ ---- -layout: page -permalink: /internal/lab/p6_gas-network-total-failure-backup-plan_bt1-2/ -shortcut: lab:p6_gas-network-total-failure-backup-plan_bt1-2 -redirect_from: - - /cards/lab:p6_gas-network-total-failure-backup-plan_bt1-2 - - /internal/cards/lab:p6_gas-network-total-failure-backup-plan_bt1-2 ---- - -# P6: Gas network total failure backup plan BT1/BT2 - -## CO2 -This process covers the actions to take in case of total failure of the carbon dioxide (CO2, dioxyde de carbone) gas network due to pipeline infrastructure breakdown. - -1. Check the CO2 connection at the back of each incubator and at the connection of the manometer to identify a possible leak. -To do so, use the leak detector spray or the gas leak detector device. - -2. Also investigate the LSRU floors - -3. If a leak can be identified, fix it: - -- plug the tubing back -- close the manometer connecting the incubator to the network (see arrow on the following picture): transfer the cells to another incubator - -<div align="center"> -<img src="p6_img_1.png"> -</div> - -4. If there no leak is detected, call 5555 and ask them to contact the SIL duty call. - -5. Notify the LCSB duty call manager and their backup by email, fill and fill the [Duty call report form](https://ulsurvey.uni.lu/index.php/936567?lang=en) - -## N2 - -This process covers the actions to take in case of total failure of the nitrogen (N2, azote) gas network due to pipeline infrastructure breakdown. -It consists in the rescue of glove boxes and hypoxic incubators by connecting them to bottles of nitrogen. - -1. Identify the pipeline infrastructure breakdown: - -- Check the “gas bottle exchange record sheet†(Appendix 03) located on the door inside the gas deposit room. -- If the N2 bottles have been changed in the last 48 h, this is indicative of a pipeline infrastructure break down. - -2. Check the N2 connection at the back of each glovebox and hypoxic incubator and at the connection of the manometer to identify a possible leak. -To do so, use the leak detector spray or the gas leak detector device. - -3. Also investigate the LSRU floors -4. If a leak can be identified, fix it: - -- plug the tubing back -- close the manometer, do not transfer the samples - -5. If there no leak is detected, call 5555 and ask them to contact the SIL duty call. -6. Notify the LCSB duty call manager and their backup by email, fill and fill the [Duty call report form](https://ulsurvey.uni.lu/index.php/936567?lang=en) \ No newline at end of file diff --git a/p6_gas-network-total-failure-backup-plan_bt1-2/p6_img_1.png b/p6_gas-network-total-failure-backup-plan_bt1-2/p6_img_1.png deleted file mode 100644 index 19cae341a69afeda8991d6e4e076bd9d9ca5b5ec..0000000000000000000000000000000000000000 Binary files a/p6_gas-network-total-failure-backup-plan_bt1-2/p6_img_1.png and /dev/null differ diff --git a/p7.2_fridge_or_freezer_failure_bta/p7.2_fridge_or_freezer_failure_bta.md b/p7.2_fridge_or_freezer_failure_bta/p7.2_fridge_or_freezer_failure_bta.md deleted file mode 100644 index d3cf48dc1cbaae0f461b3a3133d5c9c46c690478..0000000000000000000000000000000000000000 --- a/p7.2_fridge_or_freezer_failure_bta/p7.2_fridge_or_freezer_failure_bta.md +++ /dev/null @@ -1,39 +0,0 @@ ---- -layout: page -permalink: /internal/lab/p7.2_fridge_or_freezer_failure_bta/ -shortcut: lab:p7.2_fridge_or_freezer_failure_bta -redirect_from: - - /cards/lab:p7.2_fridge_or_freezer_failure_bta - - /internal/cards/lab:p7.2_fridge_or_freezer_failure_bta ---- - -# P7.2: Fridge or freezer failure BTA - -This section describes the procedure in case of alarm on fridge or freezer. - -1. Identify whether the issue comes from the **basement** or from one of the laboratories. - -- If it comes from the basement, you can take action: - - - Evaluate the origin of the alarm: door not properly closed, power failure, displaced probe… - - - If the issue cannot be fixed, - - - 4°C: transfer the content to the fridge in the same floor. Only one of the two fridges is under monitoring. If there is an issue with the temperature, transfer the content to the non-monitored fridge - - - -80°C: if there is an issue with one of the compressor, the second is able to take over and to keep the temperature at -65°C. There is no need to move the samples. - - - Keep track of what was moved where - - - Before leaving, make sure that everything is back to normal or that the transitory situation is under control - - - In case of issue, contact the facility manager - - |*Personal protective equipment*| - |:-----------------------------:| - |Lab coat| - |Gloves| - -- If it comes from any of the laboratories, contact the Mouse Facility Manager (see LCSB-INF-01 Appendix 01) and explain him the issue. - -1. Notify the Facility Manager, the LCSB duty call manager and their backup by email and fill the [Duty call report form](https://ulsurvey.uni.lu/index.php/936567?lang=en) \ No newline at end of file diff --git a/p9.2_intervention-for-emergency-situations_bta/p9.2_intervention-for-emergency-situations_bta.md b/p9.2_intervention-for-emergency-situations_bta/p9.2_intervention-for-emergency-situations_bta.md deleted file mode 100644 index 565e335d5d798f1130a4e58c63a084eab106ff9b..0000000000000000000000000000000000000000 --- a/p9.2_intervention-for-emergency-situations_bta/p9.2_intervention-for-emergency-situations_bta.md +++ /dev/null @@ -1,18 +0,0 @@ ---- -layout: page -permalink: /internal/lab/p9.2_intervention-for-emergency-situations_bta/ -shortcut: lab:p9.2_intervention-for-emergency-situations_bta -redirect_from: - - /cards/lab:p9.2_intervention-for-emergency-situations_bta - - /internal/cards/lab:p9.2_intervention-for-emergency-situations_bta ---- - -# P9.2: Intervention for emergency situations BTA - -This procedure has to be applied in the event of any problem with the animal facility, major water leak, fire or ventilation issue. - -1. Call the PC security (+352 46 66 44 5555) and explain the situation and ask them to contact the SIL duty call. - -2. If necessary, request the intervention of public rescue (112 for firemen and ambulances; 113 for the police) and be available when they arrive on site. - -3. Notify the Facility Manager, the LCSB duty call manager and their backup by email and fill the [Duty call report form](https://ulsurvey.uni.lu/index.php/936567?lang=en). \ No newline at end of file